On commercial and industrial systems the ACDB combines the outputs of several string inverters and delivers them to the building's main switchboard or a step-up transformer. A typical 100 kW panel contains three or four incoming MCBs/MCCBs, a 4P 200 A main breaker, a Type 2 AC SPD, CTs and a multifunction meter, all on tinned-copper busbars in a powder-coated or stainless steel enclosure built and type-tested to IEC 61439.
For desert sites, specify a sun shield or double-skin canopy, forced or passive ventilation with dust filters, and component ratings checked at 50 °C ambient. The panel is built to the single-line diagram of each project; the price shown is indicative for a 100 kW three-phase configuration.
The cross-section used on module leads and short rooftop string runs; 1500 V DC, halogen-free, UV-resistant.

0.6/1 kV copper XLPE-insulated, PVC-sheathed (armored on request) cable linking inverters to the AC distribution board, priced as a representative 5-core 10 mm².

Male + female IP68 PV connectors for 4–6 mm² cable, 1500 V DC, certified to IEC 62852.

Parallels two strings onto one MPPT input or cable: one male (+) and one female (−) branch, 1500 V.

Ratchet crimper with 2.5/4/6 mm² dies, insertion tool, unlocking wrenches and cable stripper.

IP65 enclosure with gPV string fuses, Type 2 DC surge protection and a load-break isolator, 1000/1500 V DC.

Rotary load-break DC switch in an IP66 enclosure for safely isolating strings ahead of the inverter.

10×85 mm photovoltaic fuse link (15–32 A) with DIN-rail fuse holder, rated to IEC 60269-6.

Y-configured MOV surge arrester with thermal disconnect and pluggable modules (In 20 kA, Imax 40 kA) for PV strings.