Every inverter output needs overcurrent and short-circuit protection that also serves as a means of isolation. For small and medium inverters this is a modular miniature circuit breaker (MCB, IEC 60898-1 / 60947-2); from about 80 A upwards, molded-case breakers (MCCB) with adjustable thermal-magnetic or electronic trip units are used.
Size the breaker at about 1.25 × the inverter's maximum continuous output current, check that its breaking capacity exceeds the prospective short-circuit current at that point, and apply the manufacturer's temperature derating, since breakers in a sun-heated outdoor panel can lose 10–15 % of their rating. The 4P 63 A C-curve unit listed here suits a 30–40 kW three-phase inverter and is used as the representative price per breaker in project estimates.
The cross-section used on module leads and short rooftop string runs; 1500 V DC, halogen-free, UV-resistant.

0.6/1 kV copper XLPE-insulated, PVC-sheathed (armored on request) cable linking inverters to the AC distribution board, priced as a representative 5-core 10 mm².

Male + female IP68 PV connectors for 4–6 mm² cable, 1500 V DC, certified to IEC 62852.

Parallels two strings onto one MPPT input or cable: one male (+) and one female (−) branch, 1500 V.

Ratchet crimper with 2.5/4/6 mm² dies, insertion tool, unlocking wrenches and cable stripper.

IP65 enclosure with gPV string fuses, Type 2 DC surge protection and a load-break isolator, 1000/1500 V DC.

Rotary load-break DC switch in an IP66 enclosure for safely isolating strings ahead of the inverter.

10×85 mm photovoltaic fuse link (15–32 A) with DIN-rail fuse holder, rated to IEC 60269-6.

Y-configured MOV surge arrester with thermal disconnect and pluggable modules (In 20 kA, Imax 40 kA) for PV strings.