Every power cable ends in a lug, and a poor termination is one of the most common causes of hot spots and fires in PV distribution boards. Tinned electrolytic-copper tube lugs (DIN 46235 or equivalent) are crimped with a hexagonal die matched exactly to the conductor size; the tin plating protects against humidity and salt air. When aluminium AC cable is used to save cost on larger inverters, bimetal lugs with a friction-welded Al barrel and Cu palm, pre-filled with contact grease, avoid the galvanic corrosion that occurs when bare aluminium touches copper.
Good practice: use the crimp tool and die specified by the lug maker, strip exactly to barrel depth, wire-brush and grease aluminium conductors, torque the bolt to the terminal manufacturer's value and mark it, and re-check with a thermal camera after the first months of operation. The box contains an assortment from 6 to 240 mm² with M6–M16 holes; single sizes are available in bulk.
The cross-section used on module leads and short rooftop string runs; 1500 V DC, halogen-free, UV-resistant.

0.6/1 kV copper XLPE-insulated, PVC-sheathed (armored on request) cable linking inverters to the AC distribution board, priced as a representative 5-core 10 mm².

Male + female IP68 PV connectors for 4–6 mm² cable, 1500 V DC, certified to IEC 62852.

Parallels two strings onto one MPPT input or cable: one male (+) and one female (−) branch, 1500 V.

Ratchet crimper with 2.5/4/6 mm² dies, insertion tool, unlocking wrenches and cable stripper.

IP65 enclosure with gPV string fuses, Type 2 DC surge protection and a load-break isolator, 1000/1500 V DC.

Rotary load-break DC switch in an IP66 enclosure for safely isolating strings ahead of the inverter.

10×85 mm photovoltaic fuse link (15–32 A) with DIN-rail fuse holder, rated to IEC 60269-6.

Y-configured MOV surge arrester with thermal disconnect and pluggable modules (In 20 kA, Imax 40 kA) for PV strings.