Medium-voltage collector cables are built to IEC 60502-2: compacted aluminium (or copper) conductor, semiconducting conductor screen, XLPE insulation, semiconducting insulation screen, copper wire or tape screen to carry earth-fault current, and an MDPE or HDPE outer sheath that resists termites and abrasion when direct-buried. The rating 18/30 (36) kV means 18 kV to earth, 30 kV phase-to-phase and 36 kV maximum system voltage — the normal choice for 33 kV networks. Three single-core cables are laid in trefoil and bonded at both ends or cross-bonded on long runs.
Sizing is dominated by thermal conditions. In GCC soils, ground temperatures of 35–40 °C at laying depth and thermal resistivity of 1.5–2.5 K·m/W for dry sand can reduce ampacity by a third compared with catalogue values; engineered thermal backfill (graded sand or weak-mix concrete) is often specified to recover rating. A 1×240 mm² aluminium circuit typically carries 15–20 MW at 33 kV; larger plants step up to 400–630 mm² or run parallel circuits. Losses are also costed over 25 years, which frequently justifies one size above the thermal minimum.
Price is per metre of single core (multiply by three per circuit). Terminations, straight joints, cable markers, warning tape and the route survey are quoted separately, and every finished circuit should pass a VLF or DC sheath test plus an AC withstand test before energisation.
The cross-section used on module leads and short rooftop string runs; 1500 V DC, halogen-free, UV-resistant.

0.6/1 kV copper XLPE-insulated, PVC-sheathed (armored on request) cable linking inverters to the AC distribution board, priced as a representative 5-core 10 mm².

Male + female IP68 PV connectors for 4–6 mm² cable, 1500 V DC, certified to IEC 62852.

Parallels two strings onto one MPPT input or cable: one male (+) and one female (−) branch, 1500 V.

Ratchet crimper with 2.5/4/6 mm² dies, insertion tool, unlocking wrenches and cable stripper.

IP65 enclosure with gPV string fuses, Type 2 DC surge protection and a load-break isolator, 1000/1500 V DC.

Rotary load-break DC switch in an IP66 enclosure for safely isolating strings ahead of the inverter.

10×85 mm photovoltaic fuse link (15–32 A) with DIN-rail fuse holder, rated to IEC 60269-6.

Y-configured MOV surge arrester with thermal disconnect and pluggable modules (In 20 kA, Imax 40 kA) for PV strings.