Above roughly 50 MW, PV plants usually export at transmission voltage (132 kV, or 220–400 kV for the largest projects). The main power transformer is designed to IEC 60076: three-phase, oil-immersed, YNd11 or YNyn0 vector group, impedance around 12–14 %, and an on-load tap changer (typically ±10 % in 1.25 % steps) so the plant can hold voltage within the grid code range as irradiance and grid conditions change. Dual ratings such as 64/80 MVA ONAN/ONAF let natural cooling cover most hours while fans add capacity at midday peaks.
Gulf specifications add 50–55 °C maximum ambient, reduced top-oil and winding temperature rises, and solar radiation on the tank, all of which raise the size and cost relative to a temperate-climate unit. Utilities also define loss capitalisation values; low no-load loss matters because the transformer stays energised every night. Accessories normally include Buchholz relay, pressure relief device, winding and oil temperature indicators, online dissolved-gas monitoring and a fire-wall with oil pit.
This is a long-lead item (often 9–15 months) and the figure shown is purely indicative for an 80 MVA 132/33 kV unit ex-works; final pricing depends on the utility's specification, loss evaluation, test programme and transport to site.
The cross-section used on module leads and short rooftop string runs; 1500 V DC, halogen-free, UV-resistant.

0.6/1 kV copper XLPE-insulated, PVC-sheathed (armored on request) cable linking inverters to the AC distribution board, priced as a representative 5-core 10 mm².

Male + female IP68 PV connectors for 4–6 mm² cable, 1500 V DC, certified to IEC 62852.

Parallels two strings onto one MPPT input or cable: one male (+) and one female (−) branch, 1500 V.

Ratchet crimper with 2.5/4/6 mm² dies, insertion tool, unlocking wrenches and cable stripper.

IP65 enclosure with gPV string fuses, Type 2 DC surge protection and a load-break isolator, 1000/1500 V DC.

Rotary load-break DC switch in an IP66 enclosure for safely isolating strings ahead of the inverter.

10×85 mm photovoltaic fuse link (15–32 A) with DIN-rail fuse holder, rated to IEC 60269-6.

Y-configured MOV surge arrester with thermal disconnect and pluggable modules (In 20 kA, Imax 40 kA) for PV strings.